01785 600 691enquiries@thecalcentre.co.uk

Save

34%

On RRP

Fluke 1736 Three-Phase Power Logger – Gold Edition

Original price was: £4,505.00.Current price is: £2,995.00. Inc VAT: £3,594.00

    3 in stock

    Calibration Certificate

    Add a 12 month Calibration Certificate

    Description

    Fluke 1736/EUS Three-Phase Power Logger Description

    The Fluke Connect-enabled Fluke 1736 Three-Phase Power Logger is an entry-level power logger optimised for electrical technicians and contractors, as well as energy saving consultants. It can be used to conduct energy studies and basic power quality logging.

    This instrument is capable of automatically capturing and logging over five-hundred power quality parameters; thereby equipping the individual with a comprehensive insight into the relevant data, allowing him/her to make critical power quality and energy decisions in real-time. The Fluke 1736 Three-Phase Power Logger is an effective inspection tool designed for optimising system reliability and savings.

    Measurement and Logging

    As indicated above the Fluke 1736 Three-Phase Power Logger is supplied with four FREE Fluke 173X-flex1500 iFlexi 1500A Probes (12 inches) which can be used to measure all three power phases and neutral. The Fluke 1736 Three-Phase Power Logger is able to identify and scale each probe. The four current probes are connected separately and can be set to 150A or 1500A, ensuring the best possible accuracy for each application.

    The Fluke 1736 Three-Phase Power Logger includes a ‘Verify Connection’ feature to ensure that probes and various test and voltage leads have been connected correctly. The Fluke 1736 Three-Phase Power Logger automatically checks whether probes and leads have been connected correctly and will digitally correct common connection errors without requiring the user to disconnect and reconnect the equipment. Furthermore, the Fluke 1736 Three-Phase Power Logger automatically alerts the user when the wrong current clamp has been connected.

    The Fluke 1736 Three-Phase Power Logger’s innovative, tangle-free and flat voltage lead also improves the simplicity and reliability of lead connections.

    Once safely connected to the system-under-investigation, the Fluke 1736 Three-Phase Power Logger will record the following parameters simultaneously:

    • RMS voltage
    • RMS current
    • Voltage and current events
    • Voltage and current THD
    • Voltage and current harmonics up to the 50th harmonic
    • Active power
    • Reactive power
    • Power factor
    • Active energy
    • Reactive energy

    (The above is a small selection of the vast array of critical three-phase power parameters that the Fluke 1736 Three-Phase Power Logger is capable of measuring and logging.)

    Measurements are logged automatically, ensuring that data trends are complete; results can be reviewed during logging sessions and/or before they are downloaded for real-time analysis. The Fluke 1736 Three-Phase Power Logger is able to save up to twenty separate logging sessions and has a memory that is large enough to record data acquired over a year.

    Downloading, Analysing and Reporting

    It is possible to download saved data for further analysis. Measurements may be downloaded to a USB flash drive, which is plugged into the side of the Fluke 1736 Three-Phase Power Logger. Alternatively, the user may view and access data via the Fluke Connect mobile app, allowing him/her to maintain a safer working distance, reducing the need for costly protective equipment.

    In addition to maintaining a safer working distance, viewing and sharing measurements with relevant persons via the Fluke Connect App allows teams to make real-time decisions. As a result, task efficiency is increased and the need for further site visits and check-ins is reduced.

    Moreover, as the user is able to monitor the Fluke 1736 Three-Phase Power Logger using a Wi-Fi enabled device, he /she can verify its functionality remotely without having to visit the site.

    Once downloaded to a PC, data can be charted, graphed and organised into reports using the Fluke Energy Analysis Plus Software. This program is equipped with a suite of powerful analysis tools allowing the user to evaluate every aspect of the energy consumption and power quality state of health. Additionally, this software can be used to create customised reports in PDF and RTF formats quickly and simply.

    Easy-to-use, Ergonomic Design

    In addition to downloading data for further analysis, the Fluke 1736 Three-Phase Power Logger features a bright, colour, touchscreen display with a graphical indication that can be used to perform in-field analysis and data checks.

    Additionally, via the display, front panel and intuitive user interface, the operator can configure (using the quick, guided, graphical setup) the Fluke 1736 Three-Phase Power Logger in order to capture the correct data for each task. Please see the following videos for further information regarding the setup and configuration of this unit.

    Alternatively, the Fluke 1736 Three-Phase Power Logger can be configured remotely using the Fluke Connect App. Both configuration methods allow the Fluke 1736 Three-Phase Power Logger to be programmed in the field, adding to the practicality and efficiency of this instrument as it does not need to be returned to a workshop for reprogramming or data download.

    Also improving this instrument’s practicality is its ability to be powered from the measured circuit.

    Applications

    The Fluke 1736 Three-Phase Power Logger’s comprehensive measurement and logging capabilities combined with its easy-to-use and practical design make it suitable for performing the following tasks.

    Load Studies

    Verify the capacity of an electrical system prior to adding loads.

    Energy Assessments

    Justify energy-saving measures by quantifying the energy consumption before and after improvements have been made to the circuit.

    Harmonic Measurements

    Determine issues caused by harmonics that are resulting in damage or disruption to critical equipment.

    Voltage and Current Event Capture

    Identify dips, swells and inrush currents that are causing false resets or nuisance circuit breaker tripping.

    The Fluke 1736 Three-Phase Power Logger is optimised for efficiency, ease-of-use and data visibility. This comprehensive, versatile instrument is the ideal entry-point model for electrical technicians, electrical contractors and energy saving consultants.

    Fluke 1736/EUS Three-Phase Power Logger Key Features

    • A Fluke Connect-enabled, entry-level power logger optimised for electrical technicians and contractors as well as energy saving consultants
    • Conduct energy studies and basic power quality logging
    • Capture and log over five-hundred parameters automatically
    • High data visibility for making critical power quality and energy decisions in real time
    • An effective inspection tool designed for optimising system reliability and savings
    • Measure all three power phases and neutral using the four FREE Fluke 173X-flex1500 iFlexi 1500A Probes (12 inches)
    • Identifies and scales each probe
    • Probes can be set to 150 A or 1500 A to ensure the best accuracy
    • ‘Verify Connection’ feature ensures that probes and test leads have been connected correctly
    • The ‘Verify Connection’ feature automatically checks for correct connections and digitally alters common connection errors without disconnecting the measurement leads
    • Automatically alerts the user when the wrong current clamp has been connected
    • Tangle-free, flat voltage lead for simple and reliable connection
    • Simultaneously logs a range of power parameters
    • RMS voltage
    • RMS current
    • Voltage and current events
    • Voltage and current THD
    • Voltage and current harmonics up to the 50th harmonic
    • Active power
    • Reactive power
    • Power factor
    • Active energy
    • Reactive energy
    • Measurements are logged automatically to ensure data trends are complete
    • Review results during logging sessions or before they are downloaded for real-time analysis
    • Save up to twenty separate logging sessions
    • Capacity to record data acquired over more than a year of logging
    • Download data to a USB flash drive
    • View and access data via the Fluke Connect App
    • Maintain a safer working distance using the Fluke Connect App reducing the need for costly protective equipment
    • Share measurements with relevant persons using the Fluke Connect App to facilitate real-time decisions
    • Fluke Connect App increases task efficiency and reduces the need for further site visits and check-ins
    • Verify the power logger’s functionality remotely via a Wi-Fi device
    • Use the Fluke Energy Analysis Plus Software to analyse every detail of the energy consumption and power quality state of health
    • Create customised reports using the Fluke Energy Analysis Plus Software
    • Bright, colour, touchscreen display with graphical indication
    • Perform in-field analysis and data checks via the display
    • Configure the logger via the front panel
    • User interface with a quick, guided, graphical setup
    • Configure the logger remotely using the Fluke Connect App
    • No need to remove the Fluke1736 from the field to configure it or download results
    • Can be powered from the circuit-under-test
    • Suitable for load studies, energy assessment, harmonic measurement and voltage and current event capture applications
    • Optimised for efficiency, ease-of-use and data visibility
    • A comprehensive and versatile entry-point power logger

    What’s Included?

    • Fluke 1736/EUS Three-Phase Power Logger
    • 4x FREE Fluke 173X-flex1500 iFlexi 1500A Probes (12 inches)
    • Fluke MP1-Magnetic Probe Set – Gold Edition ONLY
    • Power Supply
    • 4x Voltage Test Leads with Alligator Clips
    • Soft Case
    • Energy Analyse Plus Software
    • Wi-Fi Adapter
    • Line Cords
    • Colour Coding Set
    • USB Containing Instrument Documentation
    • Fluke 1736/EUS Three-Phase Power Logger inc. Software
    • 4x FREE Fluke 173X-flex1500 iFlexi 1500A Probes (12 inches)
    • Fluke MP1-Magnetic Probe Set – Gold Edition ONLY
    • Power Supply
    • 4x Voltage Test Leads with Alligator Clips
    • Soft Case
    • Energy Analyse Plus Software
    • Wi-Fi Adapter
    • Line Cords
    • Colour Coding Set
    • USB Containing Instrument Documentation

    Fluke 1736/EUS Three-Phase Power Logger Technical Specifications

    Accuracy
    ParameterRangeMax ResolutionIntrinsic Accuracy At Reference Conditions
    (% of reading + % of full scale)
    Voltage1000V0.1V±(0.2% + 0.01%)
    Currenti17xx-flex 1500 12″150A
    1500A
    0.1A
    1A
    ±(1% + 0.02%)
    ±(1% + 0.02%)
    i17xx-flex 3000 24″300A
    3000A
    1A
    10A
    ±(1% + 0.03%)
    ±(1% + 0.03%)
    i17xx-flex 6000 36″600A
    6000A
    1A
    10A
    ±(1.5% + 0.03%)
    ±(1.5% + 0.03%)
    i40s-EL clamp4A
    40A
    1mA
    10mA
    ±(0.7% + 0.02%)
    ±(0.7% + 0.02%)
    Frequency42.5Hz to 69Hz0.01Hz±(0.1%)
    Aux Input±10V DC0.1mV±(0.2% + 0.02%)
    Voltage Min/Max1000V0.1V±(1% + 0.1%)
    Current Min/MaxDefined by accessoryDefined by accessory±(5% + 0.2%)
    THD On Voltage1000%0.1%±0.5
    THD On Current1000%0.1%±0.5
    Voltage Harmonics – 2nd to 50th1000V0.1V≥10V: ±5% of reading
    <10V: ±0.5V
    Current Harmonics – 2nd to 50thDefined by accessoryDefined by accessory≥3% of current range: ±5% of reading
    <3% of current range: ±0.1% of range
    Unbalance100%0.1%±0.2
    Intrinsic Uncertainty ± (% of reading + % of range)¹
    ParameterInfluence QuantityiFlex 1500-12
    150A/1500A
    iFlex 3000-24
    300A/3000A
    iFlex 6000-36
    600/600A
    i40s-EL
    4A/40A
    Active Power
    Active Energy
    PF ≥ 0.991.2% + 0.005%1.2% + 0.0075%1.7% + 0.0075%1.2% + 0.005%
    Apparent Power
    Apparent Energy
    0 ≤ PF ≤ 11.2% + 0.005%1.2% + 0.0075%1.7% + 0.0075%1.2% + 0.005%
    Reactive Power
    Reactive Energy
    0 ≤ PF ≤ 12.5% of measured apparent power
    Power Factor
    Displacement Power Factor
    ±0.025
    Additional Uncertainly In % of RangeV P-N > 250V0.015%0.0225%0.0225%0.015%

    ¹Range = 1000V x Irange

    Electrical Specifications
    Power Supply
    Voltage Range100V to 500V using safety plug input when powering from the measurement circuit
    100V to 240V using standard power cord (IEC 60320 C7)
    Power ConsumptionMaximum 50VA (max 15VA when powered using IEC 60320 input)
    Efficiency≥68.2% (in accordance with energy efficiency regulations)
    Maximum No-Load Consumption<0.3W only when powered using IEC 60320 input
    Mains Power Frequency50/60Hz ± 15%
    BatteryLi-Ion 3.7V, 9.25Wh, customer-replaceable
    On-Battery Runtime4 hours in standard operating mode, up to 5.5 hours in power saving mode
    Charging Time<6 hours
    Data Acquisition
    Resolution16-bit synchronous sampling
    Sampling Frequency10.24kHz at 50/60Hz, synchronised to mains frequency
    Input Signal Frequency50/60Hz (42.5 to 69Hz)
    Circuit Types1-ϕ, 1-ϕ IT, split phase, 3-ϕ delta, 3-ϕ wye, 3-ϕ wye IT, 3-ϕ wye balanced, 3-ϕ
    Aron/Blondel (2-element delta), 3-ϕ delta open leg, currents only (load studies)
    Data StorageInternal flash memory (not user-replaceable)
    Memory SizeTypical 10 logging sessions of 8 weeks with 1 minute intervals and 500 events
    Basic Interval
    Measurement ParametersVoltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
    Averaging IntervalUser selectable: 1 sec, 5 sec, 10 sec, 30sec, 1 min, 5 min, 10 min, 15 min, 30 min
    Averaging Time Min/Max ValuesVoltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to
    IEC61000-4-30
    Aux, Power: 200ms
    Demand Interval
    Measured ParametersEnergy (Wh, varh, VAh), PF, maximum demand, cost of energy
    IntervalUser selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
    Power Quality Measurements
    Measured ParametersVoltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD
    Averaging Interval10 min
    Individual Harmonics2nd to 50th
    Total Harmonic DistortionCalculated on 50 harmonics
    EventsVoltage: dips, swells, interruptions
    Current: inrush current
    Triggered RecordingsFull cycle RMS updated every half cycle of voltage and current (Urms 1/2 according to IEC61000-4-30)
    Waveform of voltage and current
    Standard Compliance
    HarmonicsIEC 61000-4-7: Class 1
    IEEE 519 (short time harmonics)
    Power QualityIEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)
    PowerIEE 1459
    Power Quality ComplianceEN50160 (for measured parameters)
    Interfaces
    USB-AFile transfer via USB flash drive, firmware updates, max. supply current: 120mA
    WiFIFile transfer and remote control via direct connection or WiFi infrastructure
    BluetoothRead auxiliary measurement data from Fluke Connect 3000 series modules (requires 1738 or 1736 upgrade option)
    USB-MiniData download device to PC
    Voltage Inputs
    Number of Inputs4 (3 phases and neutral)
    Maximum Input Voltage1000 Vrms, CF 1.7
    Input Impedance10MΩ
    Bandwidth42.5Hz to 3.5kHz
    Scaling1:1 and variable
    Measurement Category1000V CAT III/600V CAT IV
    Current Inputs
    Number of Inputs4, mode selected automatically for attached sensor
    Input VoltageClamp input: 500mV rms/50mV rms; CF 2.8
    Rogowski Coil Input150mV rms / 15V mV rms at 50Hz
    180mV rms / 18mV rms at 60Hz
    CF 4
    All at nominal probe range
    Range1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12”
    3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24”
    6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36”
    40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
    Bandwidth42.5Hz to 3.5kHz
    Scaling1:1 and variable
    Auxiliary Inputs
    Number of Inputs2
    Input Range0 to ±10V DC, 1 reading/s
    Scale FactorFormat: mx + b (gain and offset) user configurable
    Displayed UnitsUser-configurable (7 characters, for example, °C, psi or m/s)
    Wireless Connection
    Number of Inputs2
    Supported ModulesFluke Connect 3000 series
    Acquisition1 reading/s
    Environmental Specifications
    Operating Temperature-10 to 50°C (14 to 122°F)
    Storage Temperature-20 to 60°C (-4 to 140°F
    With battery: -20 to 50°C (-4 to 122°F)
    Operating Humidity10 °C to 30 °C (50 °F to 86 °F) max. 95 % RH
    30 °C to 40 °C (86 °F to 104 °F) max. 75 % RH
    40 °C to 50 °C (104 °F to 122 °F) max. 45 % RH
    Operating Altitude2000m (up to 4000m derate to 1000V CAT II/600V CAT III/300V CAT IV
    Storage Altitude12000m
    EnclosureIP50 in accordance with EN60529
    VibrationMIL-T-28800E, Type 3, Class III, Style B
    SafetyIEC 61010-1
    IEC Mains Input: Overvoltage Category II, Pollution Degree 2
    Voltage Terminals: Overvoltage Category IV, Pollution Degree 2
    IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V
    Electromagnetic Compatibility (EMC)EN 61326-1: Industrial CISPR 11: Group 1, Class A
    Korea (KCC): Class A Equipment (industrial broadcasting and
    communication equipment)
    USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per
    clause 15.103
    Temperature Coefficient0.1 x accuracy specification/°C
    General Specifications
    Colour LCD Display4.3″ active matrix TFT
    480 x 272 pixels
    Resistive touch panel
    WarrantyInstrument and power supply: 2 years (battery not included)
    Accessories: 1 year
    Calibration Cycle: 2 years
    DimensionsInstrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in)
    Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in)
    Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm
    (7.8 in x 6.6 in x 3.5 in)
    WeightInstrument: 1.1 kg (2.5 lb)
    Power supply: 400 g (0.9 lb)
    Tamper ProtectionKensington lock slot

    You may also like…