Compact true-rms meter for HVAC (heating ventilation air conditioning) troubleshooting. The Fluke 116 HVAC Multimeter was specifically designed for the HVAC professional. It has everything needed in an HVAC meter including temperature and microamp measurements to quickly troubleshoot problems with HVAC equipment and flame sensors.
Fluke 116 Technical Specifications
Maximum voltage between any terminal and earth ground | |
Surge protection | | 6 kV peak per IEC 61010-1 600 V CAT III, Pollution Degree 2 |
|
Display | Digital: | 6,000 counts, updates 4 per second |
|
Bar graph | | 33 segments, updates 32 per second |
|
Operating Temperature | |
Storage Temperature | |
Battery type | | 9 volt Alkaline, NEDA 1604A/ IEC 6LR61 |
|
Battery Life | | 400 hours typical, without backlight |
|
Accuracy Specifications |
DC millivolts | Range: | 600.0 mV | Resolution: | 0.1 mV | Accuracy: | ± ([% of reading] [counts]): 0.5% 2 |
|
DC volts | Range/Resolution: | 6.000 V / 0.001 V | Range/Resolution: | 60.00 V / 0.01 V | Range/Resolution: | 600.00 V / 0.1 V | Accuracy: | ± ([% of reading] [counts]): 0.5% 2 |
|
Auto volts | Range: | 600.0 V | Resolution: | 0.1 V | Accuracy: | 2.0 % 3 (dc, 45 Hz to 500 Hz)
4.0 % 3 (500 Hz to 1 kHz) |
|
AC millivolts1 true-rms | Range: | 600.0 mV | Resolution: | 0.1 mV | Accuracy: | 1.0 % 3 (dc, 45 Hz to 500 Hz)
2.0 % 3 (500 Hz to 1 kHz) |
|
AC volts1 true-rms | Range/Resolution: | 6.000 V / 0.001 V | Range/Resolution: | 60.00 V / 0.01 V | Range/Resolution: | 600.0 V / 0.1 V | Accuracy: | 1.0 % 3 (dc, 45 Hz to 500 Hz)
2.0 % 3 (500 Hz to 1 kHz) |
|
Continuity | Range: | 600 Ω | Resolution: | 1 Ω | Accuracy: | Beeper on < 20 Ω, off > 250 Ω; detects opens or shorts of 500 μs or longer. |
|
Ohms | Range/Resolution: | 600.0 Ω / 0.1 Ω | Range/Resolution: | 6.000 kΩ / 0.001 kΩ | Range/Resolution: | 60.00 kΩ / 0.01 kΩ | Range/Resolution: | 600.0 kΩ / 0.1 kΩ | Range/Resolution: | 6.000 MΩ / 0.001 MΩ | Accuracy: | 0.9 % 1 | Range/Resolution: | 40.00 MΩ / 0.01 MΩ | Accuracy: | 1.5 % 2 |
|
Diode Test | Range/Resolution: | 2.000 V / 0.001 V | Accuracy: | 0.9% 2 |
|
Capacitance | Range/Resolution: | 1000 nF / 1 nF | Range/Resolution: | 10.00 μF / 0.01 μF | Range/Resolution: | 100.0 μF / 0.1 μF | Range/Resolution: | 9999 μF / 1 μF | Range/Resolution: | 100 μF to 1000 μF | Accuracy: | 1.9% 2 | Range/Resolution: | > 1000 μF | Accuracy: | 5% 20% |
|
LoZ capacitance | Range: | 1 nF to 500 μF | Accuracy: | 10% 2 typical |
|
Temperature2 (Type-K thermocouple) | Range/Resolution: | -40 °C to 400 °C / 0.1 °C | Accuracy: | 1% 102 | Range/Resolution: | -40 °F to 752 °F / 0.2 °F | Accuracy: | 1% 182 |
|
AC μamps true-rms (45 Hz to 500 Hz) | Range/Resolution: | 600.0 μA / 0.1 μA | Accuracy: | 1.0% 2 |
|
DC μamps | Range/Resolution: | 600.0 μA / 0.1 μA | Accuracy: | 1.0% 2 |
|
Hz (V or A input)2 | Range/Resolution: | 99.99 Hz / 0.01 Hz | Range/Resolution: | 999.99 Hz / 0.1 Hz | Range/Resolution: | 9.999 Hz / 0.001 Hz | Range/Resolution: | 50.00 Hz / 0.01 Hz | Accuracy: | 0.1% 2 |
|
Notes:
1) All ac voltage ranges except Auto-V/LoZ are specified from 1 % to 100 % of range. Auto-V/LoZ is specified from 0.0 V.
2) Temperature uncertainty (accuracy) does not include the error of the thermocouple probe.
3) Frequency is ac coupled, 5 Hz to 50 kHz for ac voltage. Frequency is dc coupled, 45 Hz to 5 kHz for ac current.
4) Temperature Range/Resolution: -40 °F to 752 °F / 0.2 °F
Mechanical & General Specifications |
Size | | 167 x 84 x 46 mm (6.57″ x 3.31″ x 1.82″) |
|
Weight | |
Warranty | |