01785 600 691enquiries@thecalcentre.co.uk

Seaward PrimeTest 250 PAT Tester – 5th Edition

£504.00 Inc VAT: £604.80

    6 in stock (can be backordered)

    Add a 12 month Calibration Certificate

    SKU 403A910 PT250+ Categories , Brand:

    Description

    Seaward PrimeTest 250+ PAT Tester

    Enabling simple, professional and fast PAT testing, this versatile tester features all of the required tests of the IET 5th Edition Code of Practice and BS EN50699, along with USB download. It is also fully compatible with the Test n Tag Pro serial printer for quick and easy label printing without any setup required – just plug and print.

    Using Seaward’s free datalogger program and pressing a single download key allows test result data to be quickly and easily transferred from the PrimeTest 250+ to PC at the press of a button.

    Data is downloaded in a simple CSV spreadsheet format for your PAT records or alternatively it can be imported directly into Seaward’s PATGuard 3 software for more enhanced record keeping, reporting and certification.

    Seaward’s unique ‘ZAP’ technology ensures that earth continuity measurements are accurate in situations where other testers struggle to provide reliable measurements, such as measuring through rust, limescale and other surface contamination.

    The PrimeTest Series Testers can be used with our free PATMobile App as part of a combined record keeping and reporting solution. The PATMobile App works with the PrimeTest 250+ to enable the input and storage of test records alongside barcode scanning, wireless label printing, photo tagging and mobile reporting.

    Built in Britain and used by 1,000’s of organisations every day.

     

    Comprehensive Range of Electrical Tests

    Capable of performing all testing procedures as required by the IET Code of Practice, this PAT tester gives quick, easy access to all testing functions via dedicated testing buttons on the front of the tester.

    The PrimeTest 250 Plus can test it all – use it to test:

    • Low current earth continuity
    • Insulation resistance at 250/500V
    • IEC leads
    • Protective conductor current
    • Touch current tests
    • 3 phase leakage current (requires 3 phase adaptor)
    • Alternative leakage
    • RCD (30mA and 150mA) and power socket tests
    • Long Lead
    • Test for Class 1 equipment with no exposed parts and a Class 2 FE test sequence to coincide with the new equipment class included in the 5th edition.

    You can use the PT250+ to test both class I and class II appliances (including IT equipment), IEC leads and extension leads and – via the use of adaptors (sold separately) – this tester is also suitable for testing 110V and 415V (3 phase) equipment.

    Manage Your Testing Records with Fully Downloadable Memory Storage

    The PrimeTest 250 Plus can store up to 999 individual appliance testing records in its internal memory. When you’ve tested something, simply press the single save key and the record will be stored, time/date stamped ready for further use.

    When you’re done testing for the day, connect your PrimeTest 250+ up to your PC using a USB cable and download the records directly onto your computer.

    The PrimeTest 250+ is one of the few downloadable PAT testers which includes its download utility as standard – records are downloaded into standard CSV format, compatible with leading spreadsheet programs such as Microsoft Excel.

    For those who require professional reports and certificates, you can also opt to purchase Seaward’s PATGuard Elite 3 software which gives you a comprehensive database of PAT records, allows you to schedule inspections and tests and create reports etc.

    Seamless Plug & Print with the Optional Test n Tag Pro Serial Printer

    Use the PrimeTest 250 Plus with the Test n Tag Pro Serial Printer (sold separately and available in kit versions of the PT250+) to create professional, low cost inspection and testing labels as you’re testing.

    The Test n Tag Pro is designed to seamlessly work with the PT250+’s memory storage capabilities; just connect up the printer when testing and hit the print button when you’re ready to print out your label.

    Every label roll for the Test n Tag Pro has over 400 labels, ensuring you can test a large amount of appliances before replacing at a later date.

    Compatible with Seaward’s PATMobile App

    The Seaward PATMobile App (available for free on GooglePlay**) is a manual data entry app designed for use with Seaward’s range of PrimeTest PAT Testers. It can be used to keep records, manage test data, and create and share CSV and PDF reports on-site.

    The Seaward PATMobile App is an effective and easy-to-use mobile app** with an eclectic array of features, including:

    • Recording and managing PAT results
    • A powerful search and filter for accessing required data
    • A dashboard for managing assets: indicates when appliances are out of date
    • Integrated calculators for risk-assessments and resistance
    • Auto-incrementation of asset IDs
    • User customisation: the user can upload a signature and/or company logo to be included in reports
    • Photos taken using the smartphone’s/ tablet’s camera can be included in records and reports
    • Scan 1D and 2D barcodes using the smartphone’s/ tablet’s camera
    • Scan Seaward’s Apollo QR codes using the smartphone’s/ tablet’s camera
    • Create PDF reports
    • Create CSV reports
    • Export CSV and PDF reports via email

    In addition to the above features and functions, the Seaward PATMobile App can be used to print labels wirelessly via Bluetooth when used in conjunction with Seaward’s Test n Tag Pro Printer and compatible labels (sold separately).

    Seaward PrimeTest 250+ PAT Tester Key Features

    • Downloadable PAT tester with internal 999 appliance record memory
    • Extremely easy to use – quick access buttons for easy test activation
    • Plug and print – simply insert Seaward’s printer (sold separately) for quick label printing
    • Date stamped results for full traceability
    • Single key save and downloading
    • Stores results in CSV format – ports directly into programs similar to Excel or Seaward’s PATGuard software
    • Low current earth continuity test to ensure accurate measurements
    • Insulation resistance test at 250 and 500V
    • IEC lead testing
    • Protective conductor current test
    • 3 phase leakage current test (requires adapter)
    • Alternative leakage current test
    • RCD test at 30mA and 150mA
    • Power socket test

    What’s Included?

    The standard version of the Seaward PrimeTest 250+ comes with:

    • 0.5m Extension Adaptor
    • Earth Lead with Probe and Clip
    • Mains Lead
    • 6 x AA Batteries
    • USB Download Lead
    • Carry Case
    • Operating Instructions
    • Downloadable PAT tester with internal 999 appliance record memory
    • Extremely easy to use – quick access buttons for easy test activation
    • Plug and print – simply insert Seaward’s printer (sold separately) for quick label printing
    • Date stamped results for full traceability
    • Single key save and downloading
    • Stores results in CSV format – ports directly into programs similar to Excel or Seaward’s PATGuard software
    • Low current earth continuity test to ensure accurate measurements
    • Insulation resistance test at 250 and 500V
    • IEC lead testing
    • Protective conductor current test
    • 3 phase leakage current test (requires adapter)
    • Alternative leakage current test
    • RCD test at 30mA and 150mA
    • Power socket test

    Seaward PrimeTest 250+ Technical Specifications

    Earth Continuity
    Output Current200mA minimum into 2Ω
    Test Voltage (o/c)9V DC nominal
    Test Duration (Class I Test)2s nominal
    Display Range0.01Ω to 19.99Ω
    Pass Value (Class I Test)0.2Ω
    Insulation Resistance
    Test Voltage250/500V DC @1mA nominal, <2mA (s/c)
    Test Duration (Class I or II)2s
    Display Range0.01MΩ to 19.99MΩ
    Pass ValueClass I: 1.0MΩ
    Class II: 2.0MΩ
    Equivalent Leakage
    Test Voltage40V Nominal AC 50Hz Open Circuit
    Test Duration2s
    Display Range0.1mA to 19.99mA
    Pass Value0.75mA/3.5mA (user selectable with 0.75mA as
    default)/0.25mA CL II
    IEC Lead Test
    Test Voltage5V DC Nominal
    Test DurationTime for Test (2s max)
    TestLive/Neutral Checks for o/c, s/c and crossed
    Protective Conductor Current
    Test VoltageSupply voltage, max current 13A
    Test Duration120s Maximum
    Display Range0.15mA to 9.99mA
    Pass Value 0.75mA/3.5mA (user selectable with 0.75mA as default)
    Touch Current
    Test VoltageSupply voltage, max current 13A
    Test Duration120s maximum
    Display Range0.10mA to 3.50mA
    Pass Value0.25mA
    3 Phase Differential Leakage Current
    *Requires 3 phase adaptor accessory
    Test Voltage3 phase supply voltage
    Test DurationContinuous measurements
    Display Range0.10mA to 9.99mA
    Pass Value 0.75mA/3.5mA (user selectable with 0.75mA as default)
    RCD Trip Time
    Test VoltageMains supply voltage
    Test Current30mA/150mA rms sinusoidal
    Test Current Phase0/180° auto switched on alternate tests
    Measuring Range0ms to 500ms
    Pass Value200ms
    Power Socket Check
    Input Voltage Range225-254V AC max current 13A UK
     Indicates configuration of voltage potential:Line to earth, line to neutral, neutral to earth
    General
    Memory Size999 Test Records
    Power Source6 x AA Batteries

    PrimeTest 250 Datasheet