01785 600 691enquiries@thecalcentre.co.uk

Save

39%

On RRP

Megger DCM305E TRMS Earth Leakage Clamp Meter

Original price was: £325.00.Current price is: £199.00. Inc VAT: £238.80

    19 in stock

    Calibration Certificate

    Add a 12 month Calibration Certificate

    SKU DCM305E-SPECIAL Categories , Brand:

    Description

    Megger DCM305E TRMS Earth Leakage Clamp Meter

    This Megger DCM305E TRMS Earth Leakage Clamp Meter is ideal for measuring the earth leakage current in a circuit where the RCD is tripping out. The clamp meter will quickly determine if the earth leakage current is causing the RCD to trip, or if it is sensitive or faulty.

    The DCM305E features a 40mm jaw and is capable of measuring both insulated and non-insulated conductors. The megger clamp meter also enables TRMS AC current measurements up to 100A and measures pure, undistorted, sinusoidal, and non-sinusoidal AC waveforms which contain pulse trains, triangles, spikes and ragged waves.

     

    Technical Specs

    Display6000 count
    Measuring FunctionTRMS Leakage current and load current
    Ranges6.000 mA / 60.00 mA / 600.00 mA / 6.000 A / 60.00 A / 100.0 A
    Basic Accuracy± (1.0 % 3d)
    AC CurrentRangeResolutionAccuracy
    6 mA0.001 mA0 ~ 10 A ±(1 % reading 8 digits)

    10 ~ 50 A ±(2 % reading 10 digits)

    50 ~ 100 A ±(10 % reading 10 digits)

    60 mA0.01 mA
    600 mA0.1 mA
    6 A0.001 A
    60 A0.01 A
    100 A0.1 A
    Frequency Response (61-400Hz) 0 ~ 10 A ±(2 % reading 11 digits)

    10 ~ 50 A ±(10 % reading 11 digits)

    50 ~ 100 A ±(35 % reading 11 digits)

    Low Pass FilterRangeResolution Accuracy 
    6 mA0.001 mA0 ~ 10 A ±(2 % reading 8 digits)

    10 ~ 50 A ±(3 % reading 10 digits)

    50 ~ 100 A ±(12 % reading 10 digits

    60 mA0.01 mA
    600 mA0.1 mA
    6 A0.001 A
    60 A0.01 A
    100 A0.1 A
    Accuracy specified at operating temperature 23° C ± 5° C <80% RH
    Resolution0.001 mA
    Operating frequency range50 – 400 Hz
    Sampling rate5 times / second
    Data, auto, peak holdUser Selectable
    Low pass filter50 / 60 Hz
    Low pass filter cut-off frequencyApproximately 100 Hz with an attenuation characteristic of approximately -24 dB / octave
    Compare pre-set limits0.25, 0.50, 3.50 mA
    Jaw size40 mm (750 mm conductor size)
    Maximum jaw opening43 mm
    Overload“OL”
    Auto power off 20 minutes of inactivity
    Operating temperature0 °C – 50 °C
    Storage temperature-20 °C – 60 °C
    Operating Altitude≤2000 m
    Temperature coefficient0.2 x (Spec. Accuracy) / °C, <18 °C, >28 °C
    Power Supply2 x 1.5 V alkaline AAA / LR03
    Battery life60 hours
    Size78 mm (W) x 203 mm (H) x 42 mm (D)
    Weight300 g
    SafetyEN61010-1 CAT III 300 V
    EMCEN61326-1

     

    • Six ranges: 6 mA, 60 mA, 600 mA, 6 A, 60 A, 100 A
    • Minimum resolution of 0.001 mA on the 6 mA range
    • Manual or Auto ranging
    • Pre-set leakage limits (0.25, 0.50, 3.5mA) visual and audible indication if limit is exceeded
    • 40mm jaw for both insulated and non-insulated conductors
    • TRMS readings
    • Low pass filter (50/60 Hz) – aids stability of readings
    • Auto-backlight, 6000 count display
    • Auto, data and peak hold for hard to read measurements
    • Analogue bar graph display for trending
    • DCM305E Earth Leakage Clamp meter
    • Carry Case