01785 600 691enquiries@thecalcentre.co.uk

Fluke 3140R Clip On Current Transformer

£551.00 Inc VAT: £661.20

    Calibration Certificate

    Add a 12 month Calibration Certificate

    SKU FLUKE 3140R Categories , Brand:

    Description

    Fluke 3140R Clip On Current Transformer

    This Fluke 3140R Clip On Current Transformer is specially designed to work seamlessly with Fluke Power Quality / RPM Full Disclosure Power Monitors. All Clamp-on CT’s are matched to take full advantage of your instrument’s ability to set scale factors for accurate readings.

    Electrical Specifications
    Reference Conditions: 23 ± 5 °C, 20 to 75 % RH; conductor
    centered in jaw opening; no DC component; no adjacent
    conductor.

    Typical Bandwidth: 5 Hz to 20 kHz
    Working Voltage: 1000 V ac rms, in compliance with
    EN61010
    Common Mode Voltage: 1000 V ac rms from earth ground, in
    compliance with EN61010
    Input Load Impedance (of host instrument): > 1 M Ω in
    parallel with up to 47 pF
    Maximum Non-destructive Current: 1000 A
    Duty Cycle: 2 A to 400 A continuous
    Influence of Adjacent Conductor: < 9.0 mA/A
    Influence of Conductor Position in Jaw Opening: ± 1.0 % of
    reading 0.05 A

    Electrical Specifications
    Typical Bandwidth5 to 20 kHz
    Working Voltage1000 V AC RMS, in compliance with EN61010
    Common Mode Voltage1000 V AC RMS from earth ground, in compliance with EN61010
    Input Load Impedance (of Host Instrument)>1 M Ω in parallel with up to 47 pF
    Maximum Non-destructive Current1000 A
    Duty Cycle2 to 400 A continuous
    Influence of Adjacent Conductor<9.0 mA/A
    Influence of Conductor Position in Jaw Opening±1.0% of reading + 0.05 A
    General Specifications
    Output Cable Length8.2′ (2.5 m)
    Maximum Conductor Size1.26″ (32 mm)
    Storage Temperature-4 to 140°F (-20 to 60°C)
    Operating Temperature32 to 122°F (0 to 50°C)
    Relative Humidity50 to 86°F (10 to 30°C): 95%
    86 to 104°F (30 to 40°C): 75%
    104 to 122°F (40 to 50°C): 45%
    Temperature Coefficient0.01% X (specified accuracy)/ °C (<18°C or >28°C)
    AltitudeOperating: 6561.68′ (2000 m)
    6561.68 to 13,123.36′ (2000 to 4000 m), derate category rating to 1000 V CAT II/600 V CAT III
    Non-operating: 39,370.079′ (12000 m)
    Dimensions5.9 x 2.75 x 1.18″ (150 x 70 x 30 mm)
    Weight0.25 lb (114 g)
    • CT Type – Clamp On
    • Current Range – 2 to 400Amps
    • Accuracy – 2 percent RDG +/- 0.04 Amps
    • Frequency Response – 20 KiloHertz
    • Jaw Opening – 3.2 centimeters (1.25 inches)