Description
Amprobe AMP-320-EUR TRMS Clamp Multimeter w/ Motor Testing
Designed for professional electricians and with built-in multimeter capabilities, the Amprobe AMP-320-EUR TRMS Clamp Multimeter can measure AC/DC voltage to 600V within 1.0% accuracy, along with AC current to 600A within 1.8% accuracy, DC voltage to 600V to 1% accuracy and AC/DC current to 600A within 2.2% accuracy.
The upgraded version of the AMP-310-EUR, the Amprobe AMP-320-EUR can measure AC/DC current whereas the previous model can only measure AC current.
Also, the AMP-320-EUR comes with True-RMS functions along with motor testing capabilities such as motor rotation, 3-phase sequence testing and inrush current monitoring during motor start-up.
Not only does it come with motor testing capabilities, it also has HVAC features such as temperature measurements (°F or °C), DC microamps for flame sensor testing and capacitance measurements. Additional functions included with the AMP-320-EUR are low pass filter, autoranging and relative zero, MAX/MIN/AVG and diode tests. It also comes with a backlight function for use in darkened environments, along with the auto power off mode which will help save the battery life of your clamp meter. Also you can use the Amp-tip function for measuring precise lower currents down to 0.1A, which helps with electrical system troubleshooting.
You can use the 35mm jaw opening to clamp around wires, or you can use the multimeter functions with the included test leads to carry out your measurements.
Amprobe AMP-320-EUR TRMS Clamp Multimeter Technical Specifications
Safety Rating | CAT III 600 V |
Jaw Opening | 1.37 in (35 mm) |
AC Voltage (True-RMS) | Range: 0 to 600.0 V Accuracy: ±1.0% 5LSD (50 to 60 Hz) |
DC Voltage | Range: 0 to 600.0 V Accuracy: ±1.0% 5LSD |
AC DC Voltage | Range: 0 to 600.0 V Accuracy: 1.2% ± 7LSD (DC, 50 to 60 Hz) |
AC Current (True-RMS) | Range: 0 to 600.0 A Accuracy: ±1.8% 5LSD (50 to 100 Hz) ±2.0% 5LSD (100 to 400 Hz) |
DC Current | Range: 0 to 600.0 A Accuracy: ±2.0% 5LSD |
AC DC Current | Range: 0 to 600.0 A Accuracy: ±2.2% 7LSD (DC, 50 to 100 Hz) ±2.7% 7LSD (100 to 400 Hz) |
Precise Low Current AC | Range: 0 to 60.00 A Accuracy: ±1.5% 5LSD (50 to 60 Hz) |
Precise Low Current DC | Range: 0 to 60.00 A Accuracy: ±2.0% 5LSD |
Precise Low Current AC DC | Range: 0 to 60.00 A Accuracy: ±2.0% 5LSD (DC, 50 to 60 Hz) |
Frequency | Range: 5.00 to 999.9 Hz Accuracy: ±1.0% 5LSD (600 V range) Range: 50.0 to 400.0 Hz Accuracy: ±1.0% 5LSD (600 A range) |
Resistance | Range: 0.0 to 60.00 kΩ Accuracy: ±1.0% 5LSD |
Capacitance | Range: 0.0 to 2500 μF Accuracy: ±2.0% 4LSD |
Continuity Beeper | ON ≤ 10 Ω OFF > 250 Ω |
Non-Contact Voltage | 20 to 440 V, 50/60 Hz |
DC Microamps | Range: 0.0 to 2000 μA Accuracy: ±1.0% 5LSD |
Temperature | Range: -40.0 to 752°F, -40.0 to 400°C Accuracy: -40.0 to 14.0°F (±1.0% 3.0°F), >14.0 to 99.9°F (±1.0% 1.5°F) 100 to 752°F (±1.0% 2°F), -40.0 to -10.0°C (±1.0% 1.5°C) >-10.0 to 99.9°C (±1.0% 0.8°C), 100 to 400°C (±1.0% 1°C) |
General Specifications | |
Display | 3-5/6 digits 6000 counts |
Polarity | Automatic |
Update Rate | 5 per second nominal |
Operating Temperature | 32 to 104°F (0 to 40°C) |
Relative Humidity | 80% at 30°C, 50% at 40°C |
Operating Altitude | 0 to 2000 m |
Pollution Degree | 2 |
Storage Temperature | -4 to 140°F (-20°C to 60°C), < 80% RH |
Temperature Coefficient | Nominal 0.15 x (specified accuracy)/ °C @ (0°C to 18°C or 28°C to 40°C) |
Battery | Two AAA 1.5 V battery |
EMC | Meets EN 61326-1:2006 |
Safety Compliance | UL/IEC/EN 61010-1 ed. 3.0, IEC/ EN 61010-2-033 ed. 1.0, CAN/CSA C22.2 NO. 61010-1 ed. 3.0, IEC/ EN 61010-2-032 ed. 3.0 & IEC/EN 61010-031 ed. 1.1 |
Certification | UL (c/us) and CE |
Dimensions (L x W x H): | 8.82 x 3.03 x 1.46 in (224 x 77 x 37 mm) |